Chapter 2
284
External Device Setup Manual
7.4 Environment Settings
7.4.1 Using Computer Link Module
7.4.2 Using Communication Port
Item Setting
Interface RS485 2-wire (Set DIP switch SW3-2 to OFF)
RS485 4-wire (Set DIP switch SW3-2 to ON)
Communication Mode Computer Link (Command mode) (Set DIP switch SW0 to”4”)
Station No. Set to the same setting as the
MICRO/I
01 to 17(oct) (Set DIP switch SW1 / SW2)
Data Bits 7 (fixed)
Baud Rate [bps] 1200, 2400, 4800, 9600 or 19200 (Set DIP switch SW4)
Parity Even or Odd (Set DIP switch SW3-4)
Stop Bits 2 (fixed)
Item Setting
Interface RS232C, RS422/485
Station No. Set to the same setting as the
MICRO/I
001 to 037(oct) (Set System Memory #235/#237)
Data Bits 7 (fixed)
Baud Rate [bps] 1200, 2400, 4800, 9600, 19200, 38400, 57600 or 115200
(Set the bit position D2D1D0 System Memory of #234/#236)
Parity Even, Odd or None (Set the bit position D4D3 of System Memory #234/#236)
Stop Bits 1 or 2 (Set the bit position D5 of System Memory #234/#236)
- Set System Memory #234 for communication conditions of PLC (JW30 Communication port1: RS422), and set System
Memory #235 for Station No.
- Set System Memory #236 for communication conditions of PLC (JW20/70/100 Communication port, JW30
Communication port2: RS232C, RS422), and set System Memory #237 for Station No.
- Confirm the PLC manuals as the speed of Baud Rate may not use according to PLC.
- When connecting with the communication port of a CPU unit and making it communicate, after receiving a response from
PLC depending on the model of PLC, while MICRO/I transmit data, some which need waiting time are. In this time,
please adjust Configuration - System Setup - Project - Host I/F Driver - transmission wait of WindO/I-NV2.
Confirm the manual. (chapter of a communication port) of PLC about whether a transmitting wait setup need to be
adjusted.
- Refer to “New Satellite JW manual “or “New Satellite JW Link Unit manual” for details.